Product details : 

  • Application : Extended service life of system due to temperature and current monitoring
  • Supply voltage : AC 115-240V
  • Permitted ambient temperature : -30...+70°C
  • Reset delay: Overvoltage : 1min ±6s
  • Reset of reset delay : Main reset >5s only possible if there is no error current
  • Relay: Connection : 240V ~ 2.5A C300Min. 24V ~ / 20mA
  • Relay: Mechanical service life : Approx. 1 million switching cycles
  • Interface : Diagnose port (DP)
  • Protection class acc. To EN 60529 : IP00
  • Connection type : 6.3mm flat plugs
  • Housing material : PA glass-fibre-reinforced
  • Mounting : Screw mounted
  • Dimensions : See dimensions in mm
  • Weight : Approx. 200g
  • Check base : EN 61000-6-2, EN 61000-6-3 EN 61010-1 Overvoltage category II Pollution level 2
  • Mains voltage monitoring: Monitoring range 1 : AC 110-120V
  • Mains voltage monitoring: Monitoring range 1, Mains voltage recognition : ≤150V
  • Mains voltage monitoring: Monitoring range 1, Accuracy : ±5% of the measuring range
  • Mains voltage monitoring: Monitoring range 1, Undervoltage preliminary warning : <103V
  • Mains voltage monitoring: Monitoring range 1, Undervoltage shutdown : <98V
  • Mains voltage monitoring: Monitoring range 1, Overvoltage preliminary warning : >127V
  • Mains voltage monitoring: Monitoring range 1, Overvoltage shutdown : >132V
  • Mains voltage monitoring: Monitoring range 2 : AC 220-240V
  • Mains voltage monitoring: Monitoring range 2, Mains voltage recognition : >150V
  • Mains voltage monitoring: Monitoring range 2, Accuracy : ±5% of the measuring range
  • Mains voltage monitoring: Monitoring range 2, Undervoltage preliminary warning : <187V
  • Mains voltage monitoring: Monitoring range 2, Undervoltage shutdown : <177V
  • Mains voltage monitoring: Monitoring range 2, Overvoltage preliminary warning : >244V
  • Mains voltage monitoring: Monitoring range 2, Overvoltage shutdown : >265V
  • Reset delay: Undervoltage : 1min ±6s