KRIWAN INT69 TM Diagnose Article-Nr.: 22 A 418 S80
Product details :
- Application : Medium and large semi-thermal piston compressors
- Functions : Motor temperature static, Motor temperature dynamic, Short circuit, Reset delay
- Supply voltage : AC 115-230V
- Permitted ambient temperature : -30...+70°C
- Temperature measuring circuits: Type : 1-2 AMS sensors in series alternative 1-9 PTC sensors acc. to DIN 44081, DIN 44082 in series
- Temperature measuring circuits: R_25, total : <1.8kΩ
- Temperature measuring circuits: R_trip, static : 4.5kΩ ±20%
- Temperature measuring circuits: R_reset : 2.75kΩ ±20%
- Temperature measuring circuits: Max. length connection line : 30m
- Short circuit monitoring system PTC : Typically <30Ω
- Input, operating recongnition motor: Lower limit : AC 100V at 20Hz to 175V at 90Hz
- Input, operating recongnition motor: Upper limit : AC 460V ±15%
- Reset delay: Motor temperature static : 5min ±1min
- Reset delay: Motor temperature dynamic : 5min ±1min
- Resetting the lock or the reset delay : Main reset >5s only possible if there is no error current
- Relay: Connection : AC 240V 2.5A C300 at least AC/DC 24V 20mA
- Relay: Mechanical service life : Approx. 1 million switching cycles
- Interface : Diagnose port (DP)
- Protection class acc. To EN 60529 : IP00
- Connection type : Flat plug sleeves (operating recognition) screw terminals
- Housing material : PA glass-fibre-reinforced
- Mounting : Can be snapped onto 35mm standard rail acc. to EN 60715 or screw mounted
- Dimensions : Refer to dimensions in mm
- Weight : Approx. 200g
- Check base : EN 61000-6-2, EN 61000-6-3 EN 61010-1 Overvoltage category II Pollution level 2
- Approval : UL File No. E75899 cURus