KRIWAN INT69 U2 Diagnose Article-Nr.: 22 A 636 S021
Product details :
- Application : Extended service life of system due to temperature and current monitoring
- Supply voltage : AC 115-240V
- Permitted ambient temperature : -30...+70°C
- Temperature measuring circuits: Type : 1-2 AMS sensors in series alternative 1-9 PTC sensors acc. to DIN 44081, DIN 44082 in series
- Temperature measuring circuits: R_25, total : <1.8kΩ
- Temperature measuring circuits: R_trip, static : 4.5kΩ ±20%
- Temperature measuring circuits: R_reset : 2.75kΩ ±20%
- Temperature measuring circuits: Max. length connection line : 10m
- Short circuit monitoring system PTC : Typically <30Ω
- Reset delay: Motor temperature static : 30min ±5min
- Reset delay: Overvoltage : 1min ±6s
- Reset of reset delay : Main reset >5s only possible if there is no error current
- Relay: Connection : 240V ~ 2.5A C300Min. 24V ~ / 20mA
- Relay: Mechanical service life : Approx. 1 million switching cycles
- Interface : Diagnose port (DP)
- Protection class acc. To EN 60529 : IP00
- Connection type : 6.3mm flat plugs
- Housing material : PA glass-fibre-reinforced
- Mounting : Screw mounted
- Dimensions : See dimensions in mm
- Weight : Approx. 200g
- Check base : EN 61000-6-2, EN 61000-6-3 EN 61010-1 Overvoltage category II Pollution level 2
- Mains voltage monitoring: Monitoring range 1 : AC 110-120V
- Mains voltage monitoring: Monitoring range 1, Mains voltage recognition : ≤150V
- Mains voltage monitoring: Monitoring range 1, Accuracy : ±5% of the measuring range
- Mains voltage monitoring: Monitoring range 1, Undervoltage preliminary warning : <103V
- Mains voltage monitoring: Monitoring range 1, Undervoltage shutdown : <98V
- Mains voltage monitoring: Monitoring range 1, Overvoltage preliminary warning : >127V
- Mains voltage monitoring: Monitoring range 1, Overvoltage shutdown : >132V
- Mains voltage monitoring: Monitoring range 2 : AC 220-240V
- Mains voltage monitoring: Monitoring range 2, Mains voltage recognition : >150V
- Mains voltage monitoring: Monitoring range 2, Accuracy : ±5% of the measuring range
- Mains voltage monitoring: Monitoring range 2, Undervoltage preliminary warning : <187V
- Mains voltage monitoring: Monitoring range 2, Undervoltage shutdown : <177V
- Mains voltage monitoring: Monitoring range 2, Overvoltage preliminary warning : >244V
- Mains voltage monitoring: Monitoring range 2, Overvoltage shutdown : >265V
- Reset delay: Undervoltage : 1min ±6s