KRIWAN INT69 KF2 Diagnose Article-Nr.: 22 A 622 S80, 31 A 622 S80
Product details :
- Application : Compressors acc. IEC/EN 60335
- Functions : Motor temperature static, Motor temperature dynamic, Short circuit
- Supply voltage : AC 24-240V
- Permitted ambient temperature : -30...+70°C
- Temperature measuring circuits: Type : 1-2 AMS sensors in series alternative 1-9 PTC sensors acc. to DIN 44081, DIN 44082 in series
- Temperature measuring circuits: R_25, total : <1.8kΩ
- Temperature measuring circuits: R_trip, static : 4.5kΩ ±20%
- Temperature measuring circuits: R_reset : 2.75kΩ ±20%
- Temperature measuring circuits: Max. length connection line : 30m
- Short circuit monitoring system PTC : Typically <30Ω
- Reset delay: Motor temperature static : 30min ±5min
- Reset of reset delay : Main reset >5s only possible if there is no error current
- Relay: Connection : Refer to wiring diagram Max. 2.5A C300
- Relay: Mechanical service life : Approx. 1 million switching cycles
- Interface : Diagnose port (DP)
- Protection class acc. To EN 60529 : IP00
- Connection type : 6.3mm flat plugs
- Housing material : PA glass-fibre-reinforced
- Mounting : Screw mounted
- Dimensions : Refer to dimensions in mm
- Weight : Approx. 200g
- Check base : IEC/EN 60335, IEC/EN 60730, UL 60730 EN 61000-6-2, EN 61000-6-3 EN 61010-1 Overvoltage category II Pollution level 2
- Approval : UL File no. E75899 cURus VDE certification no. 40022017
- Reset delay : 30min ±5min